STA, DSTA, SWA and AWA constructions from 0.6/1kV, 4 to 400 mm², for direct burial and exposed outdoor routes.
Get a Quote Technical Parameters
Armoured LV Cables
Armoured cable is specified when the route itself is the risk: buried ducts, factory yards, cable trenches shared with traffic, or areas where rodents and impact are a real possibility. The armour is a galvanised steel tape or wire layer under the outer sheath, bonded to earth at both ends so it also acts as a fault-current path.
Armoured cable constructions
Each product can be supplied to the standard construction or adapted to the project specification.

Steel Tape Armoured LV Cable
STA and DSTA 0.6/1kV cable for direct burial and exposed routes: XLPE insulation, PVC bedding, galvanised steel tape, PE or PVC outer sheath.
View product →Related families
Often specified alongside this range.
LV Power Cables (0.6/1kV)
Copper or aluminium conductors, PVC or XLPE insulation, 1 to 5 cores, 1.5 to 630 mm², with PVC, PE or LSZH sheathing.
View rangeLSZH Flame Retardant
Halogen-free, low smoke compounds for escape routes, tunnels and spaces where corrosive gas would damage equipment.
View rangeFlexible Industrial Cables
Fine-strand conductors and PUR or PVC sheaths for continuous flexing in drag chains, robots and moving machine parts.
View rangeConstruction and ratings
| Rated voltage | 0.6/1 kV (U0/U) |
|---|---|
| Armour type | STA (single steel tape), DSTA (double tape), SWA (steel wire), AWA (aluminium wire) |
| Cores | 1 – 5 cores, 3+1, 4+1 |
| Cross-section | 4 – 400 mm² |
| Insulation | XLPE or PVC |
| Inner covering | Extruded PVC bedding over the laid-up cores |
| Outer sheath | PVC ST2 or PE, black, 1.8 – 3.0 mm nominal |
| Standard | IEC 60502-1, IEC 60228 |
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsWhat the construction gives you
- Galvanised steel tape gives radial protection against impact and rodent attack; steel wire adds tensile strength for vertical or long pulls.
- The armour is earthed at both ends and carries fault current, so it must be sized with the earthing design — not treated as packaging.
- PE outer sheath is the default for direct burial; PVC ST2 is used where flame retardance matters more than soil resistance.
- Bending radius is larger than unarmoured cable: allow 12 × overall diameter for tape armour and 15 × for wire armour.
- Terminations use standard armoured glands with an earth tag; we can supply glands and lugs with the cable order.
Applications
Direct burial
Buried feeders to workshops, pump houses and site buildings without a duct system.
Outdoor yards
Routes crossing vehicle areas, storage yards and exposed industrial ground.
Cable trenches
Shared trenches and culverts where mechanical damage during later works is likely.
Vertical risers
Wire-armoured constructions for shafts where the cable weight must be carried by the armour.
Frequently asked questions
Steel tape or steel wire armour?
Is the armour suitable as an earth conductor?
What sheath should I specify for wet ground?
Can armoured cable be installed in a duct?