Fire Resistant LV Cables
Mica-barrier constructions tested to IEC 60331 and BS 6387 CWZ for emergency lighting, pumps and life-safety systems.
Get a Quote Technical Parameters
Fire Resistant LV Cables
Fire resistant cable is not the same as flame retardant cable. Flame retardant cable resists ignition and stops flame spreading; fire resistant cable keeps working while the fire is still burning. The difference is a mica tape barrier around the conductor that sinters into an insulating shell when the polymer burns away, so the circuit stays live long enough for evacuation, pumps, lifts and smoke control.
Fire resistant cable constructions
Each product can be supplied to the standard construction or adapted to the project specification.

Fire Resistant LV Power Cable
Mica tape barrier over the conductor, XLPE insulation and LSZH sheath, tested to IEC 60331 and BS 6387 CWZ for fire survival circuits.
View product →Related families
Often specified alongside this range.
LV Power Cables (0.6/1kV)
Copper or aluminium conductors, PVC or XLPE insulation, 1 to 5 cores, 1.5 to 630 mm², with PVC, PE or LSZH sheathing.
View rangeArmoured LV Cables
STA, DSTA, SWA and AWA constructions from 0.6/1kV, 4 to 400 mm², for direct burial and exposed outdoor routes.
View rangeLSZH Flame Retardant
Halogen-free, low smoke compounds for escape routes, tunnels and spaces where corrosive gas would damage equipment.
View rangeConstruction and ratings
| Rated voltage | 0.6/1 kV (U0/U) |
|---|---|
| Cores | 1 – 5 cores, 3+1, 4+1 |
| Cross-section | 1.5 – 300 mm² |
| Fire barrier | Mica glass tape lapped over the conductor |
| Insulation | XLPE over the mica barrier |
| Sheath | LSZH or PVC, low smoke options |
| Fire resistance | IEC 60331-21 (750 °C), BS 6387 CWZ (950 °C, water, mechanical shock) |
| Flame propagation | IEC 60332-3-24 Cat. C |
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsWhat the construction gives you
- The mica tape is the functional layer: without it the cable may pass a flame test but will not maintain circuit integrity.
- BS 6387 CWZ adds water spray (W) and mechanical shock (Z) to the temperature test, which is the usual requirement for life-safety systems.
- Combine with LSZH sheathing where smoke and corrosive gas are also a concern, as in tunnels and high-rise buildings.
- Circuit integrity depends on the supports and glands as much as the cable — use fire-rated supports and keep the route protected.
- We supply test reports with each batch for project handover documentation.
Applications
Emergency lighting
Escape route and exit sign circuits that must operate during evacuation.
Fire pumps
Pump house feeders and control circuits required to run during a fire.
Smoke control
Pressurisation fans, dampers and extract systems in buildings and tunnels.
Alarm & life safety
Fire alarm panel feeders, lift homing and public address systems.
Frequently asked questions
What is the difference between FR and FR-LSZH cable?
Which standard should I quote: IEC 60331 or BS 6387?
Does the cable need a special gland?
Can fire resistant cable be buried?
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsNeed Fire Resistant LV Cables for a Project?
Send the cable schedule and the delivery port. We will confirm construction, standard and lead time with the quotation.