Fire Resistant LV Cables

Mica-barrier constructions tested to IEC 60331 and BS 6387 CWZ for emergency lighting, pumps and life-safety systems.

Get a Quote Technical Parameters
Fire resistant LV cable with mica tape barrier
Category 05

Fire Resistant LV Cables

Fire resistant cable is not the same as flame retardant cable. Flame retardant cable resists ignition and stops flame spreading; fire resistant cable keeps working while the fire is still burning. The difference is a mica tape barrier around the conductor that sinters into an insulating shell when the polymer burns away, so the circuit stays live long enough for evacuation, pumps, lifts and smoke control.

0.6/1 kVMica barrier1.5–300 mm²IEC 60331BS 6387 CWZLSZH
Request a Quotation
Technical parameters

Construction and ratings

Rated voltage0.6/1 kV (U0/U)
Cores1 – 5 cores, 3+1, 4+1
Cross-section1.5 – 300 mm²
Fire barrierMica glass tape lapped over the conductor
InsulationXLPE over the mica barrier
SheathLSZH or PVC, low smoke options
Fire resistanceIEC 60331-21 (750 °C), BS 6387 CWZ (950 °C, water, mechanical shock)
Flame propagationIEC 60332-3-24 Cat. C
Values are for the standard construction. Current ratings depend on installation method, ambient temperature and grouping — confirm against IEC 60364-5-52 before finalising the section.

Request datasheet & price

Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.

Get a Quote WhatsApp Us
Response< 24 h
MOQOn request
Performance

What the construction gives you

  • The mica tape is the functional layer: without it the cable may pass a flame test but will not maintain circuit integrity.
  • BS 6387 CWZ adds water spray (W) and mechanical shock (Z) to the temperature test, which is the usual requirement for life-safety systems.
  • Combine with LSZH sheathing where smoke and corrosive gas are also a concern, as in tunnels and high-rise buildings.
  • Circuit integrity depends on the supports and glands as much as the cable — use fire-rated supports and keep the route protected.
  • We supply test reports with each batch for project handover documentation.
Where it is used

Applications

Emergency lighting

Escape route and exit sign circuits that must operate during evacuation.

Fire pumps

Pump house feeders and control circuits required to run during a fire.

Smoke control

Pressurisation fans, dampers and extract systems in buildings and tunnels.

Alarm & life safety

Fire alarm panel feeders, lift homing and public address systems.

Technical FAQ

Frequently asked questions

What is the difference between FR and FR-LSZH cable?
Both maintain circuit integrity. FR-LSZH adds a halogen-free low-smoke sheath, which is specified where corrosive gas and smoke would endanger evacuees or damage equipment. In tunnels and public buildings, FR-LSZH is normally the default.
Which standard should I quote: IEC 60331 or BS 6387?
IEC 60331-21 is the common international baseline at 750 °C. BS 6387 CWZ is stricter because it adds water spray and mechanical shock. Gulf and Asian projects often accept IEC; UK-influenced and life-safety specifications usually ask for CWZ.
Does the cable need a special gland?
Use a fire-rated gland and maintain the manufacturer’s strip length so the mica barrier is not damaged during termination. Poor termination is the most common cause of circuit-integrity failure in service.
Can fire resistant cable be buried?
It can be installed underground, but the fire barrier adds cost without benefit in a buried route. Use it where a fire exposure is credible and keep the buried section in a standard armoured construction.

Request datasheet & price

Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.