Fire Resistant Power Cable, 0.6/1kV
0.6/1kV cable with a mica glass tape barrier over each conductor, XLPE insulation and an LSZH sheath, for circuits that must keep working during a fire.
Construction and behaviour
Fire resistant cable is built around one functional layer: the mica glass tape wrapped directly over the conductor. When the insulation burns away, the mica sinters into a ceramic shell that still separates the conductor from earth, so the circuit keeps conducting while the fire continues.
That is why the position of the barrier matters. A cable with a fire retardant sheath but no mica layer will resist flame spread and still lose circuit integrity within minutes. When a specification asks for fire resistance, the question to ask is which test and which barrier.
The common tests are IEC 60331-21 at 750 °C for 90 minutes, and BS 6387 categories CWZ, which add water spray (W) and mechanical shock (Z) at 950 °C. Life-safety systems in tunnels, high-rise buildings and hospitals are normally specified to CWZ.
We build the cable with XLPE over the mica barrier and an LSZH sheath as standard, so the same cable addresses smoke density and corrosive gas as well as circuit integrity. Test reports are supplied with the batch documents.
Specification table
| Standard | IEC 60502-1, IEC 60331-21, BS 6387 CWZ |
|---|---|
| Rated voltage | 0.6/1 kV (U0/U) |
| Conductor | Class 1 or Class 2 copper |
| Cross-section | 1.5 – 300 mm² |
| Fire barrier | Mica glass tape, lapped over conductor |
| Insulation | XLPE |
| Sheath | LSZH (standard) or PVC |
| Fire resistance | IEC 60331-21 750 °C / 90 min; BS 6387 C, W, Z at 950 °C |
| Flame propagation | IEC 60332-3-24 Cat. C |
| Smoke & halogen | IEC 61034, IEC 60754 |
| Packing | Drum, project lengths |
Available constructions
| Construction | Typical use |
|---|---|
| Cu / mica / XLPE / LSZH | Standard fire survival cable for indoor life-safety circuits. |
| Cu / mica / XLPE / LSZH + STA | Fire resistant with steel tape armour for buried or exposed sections. |
| Cu / mica / XLPE / PVC | Fire resistance where LSZH is not required. |
| Screened FR | Fire resistant with copper screen for control and alarm circuits. |
Where it is used
- Emergency lighting — Exit signs, escape route lighting and standby circuits.
- Fire pumps — Pump feeders and control circuits required to run during a fire.
- Smoke control — Pressurisation fans, dampers and extract systems.
- Life safety systems — Fire alarm feeders, lift homing and public address.
How it ships
- Drums sealed against moisture for sea freight.
- Batch test reports for IEC 60331 / BS 6387 included with documents.
- Fire-rated glands and supports can be quoted with the cable.
- Drum schedule issued before shipment.
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsQuestions buyers ask about this cable
What is the difference between fire resistant and flame retardant?
Which test should be specified?
Does the mica barrier affect current rating?
Can it be terminated with standard glands?
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsOften specified with this cable
Related constructions from the same or a neighbouring family.
All products
LSZH Flame Retardant LV Cable
0.6/1kV XLPE cable with a halogen-free low-smoke sheath, tested to IEC 60754 and IEC 61034 for tunnels and public buildings.
View product →
0.6/1kV PVC/XLPE Insulated LV Power Cable
The general-purpose 0.6/1kV cable for final circuits: copper conductor, PVC or XLPE insulation, 1 to 5 cores, PVC, PE or LSZH sheath.
View product →Request a quotation for Fire Resistant LV Power Cable
Share the application, voltage, core count, conductor size, screen or armour, sheath and delivery destination. Our engineering team replies within one business day.