LSZH LV Cable, 0.6/1kV
0.6/1kV XLPE insulated cable with a halogen-free low-smoke sheath, for routes where smoke density and corrosive gas are part of the fire strategy.
Construction and behaviour
LSZH cable is specified by the fire strategy, not by the electrical load. The conductor and insulation are conventional; the difference is the sheath compound, which contains no halogens and is formulated to produce limited smoke and non-corrosive combustion products.
The practical consequences are measurable. Light transmittance above 60 % to IEC 61034 means people can still see exit signs in a smoke-filled corridor. A hydrogen chloride content below 0.5 % to IEC 60754 means the acid gas will not attack steelwork, switchgear or the electronics in an adjacent room.
The trade-off is mechanical. LSZH compounds are generally softer and less abrasion-resistant than PVC, and they cost more. Support spacing and pulling tension should follow the datasheet rather than PVC habits, and the sheath should not be dragged over sharp tray edges during installation.
For projects in the EU, the CPR classification under BS EN 50575 is the usual way to specify performance. We can supply cables with a declared Euroclass and the associated declaration of performance.
Specification table
| Standard | IEC 60502-1, IEC 60228, BS EN 50575 (CPR on request) |
|---|---|
| Rated voltage | 0.6/1 kV (U0/U) |
| Conductor | Class 1 or Class 2 copper |
| Cross-section | 1.5 – 400 mm² |
| Insulation | XLPE (90 °C); LSZH compound on smaller sections |
| Sheath | Halogen-free LSZH compound |
| Smoke density | IEC 61034-2, transmittance ≥ 60 % |
| Halogen content | IEC 60754-1 ≤ 0.5 %; IEC 60754-2 pH ≥ 4.3, conductivity ≤ 10 µS/mm |
| Flame propagation | IEC 60332-1-2; IEC 60332-3-24 Cat. C |
| Temperature range | −15 °C to +90 °C |
| Packing | Drum, 500 m / 1000 m or project lengths |
Available constructions
| Construction | Typical use |
|---|---|
| Cu / XLPE / LSZH | Standard LSZH power cable for indoor routes and risers. |
| Cu / XLPE / LSZH + STA | LSZH with steel tape armour for buried or exposed sections. |
| Cu / XLPE / LSZH (FR) | Combined fire resistant and low smoke construction for life-safety circuits. |
| Al / XLPE / LSZH | Large feeders where weight and cost are decisive. |
Where it is used
- Metro & tunnel — Lighting, ventilation and signalling feeders along escape routes.
- Airports & stations — Terminals, concourses and service corridors with high occupancy.
- Hospitals & schools — Areas where smoke and acid gas would endanger occupants.
- Data & control rooms — Protection of sensitive equipment from corrosive combustion products.
How it ships
- Drums sealed against moisture for sea freight.
- Length marking every metre on request.
- Test reports for smoke density and halogen content included with the batch documents.
- Drum schedule issued before shipment.
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsQuestions buyers ask about this cable
Does LSZH mean the cable will not burn?
Can I use LSZH cable outdoors?
Is there a price difference against PVC?
Can you provide a CPR declaration?
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsOften specified with this cable
Related constructions from the same or a neighbouring family.
All products
Fire Resistant LV Power Cable
Mica tape barrier over the conductor, XLPE insulation and LSZH sheath, tested to IEC 60331 and BS 6387 CWZ for fire survival circuits.
View product →
0.6/1kV PVC/XLPE Insulated LV Power Cable
The general-purpose 0.6/1kV cable for final circuits: copper conductor, PVC or XLPE insulation, 1 to 5 cores, PVC, PE or LSZH sheath.
View product →
Shielded LV Power Cable
0.6/1kV cable with copper tape or wire screen and drain wire for VFD outputs, EMI-heavy plants and sensitive equipment feeds.
View product →Request a quotation for LSZH Flame Retardant LV Cable
Share the application, voltage, core count, conductor size, screen or armour, sheath and delivery destination. Our engineering team replies within one business day.