Aluminum Conductor LV Cable, 0.6/1kV
0.6/1kV aluminium conductor cable, XLPE insulated, 16 to 400 mm², for long feeders where conductor weight and cost dominate the selection.
Construction and behaviour
Aluminium conductor cable is chosen for two reasons: weight and cost. Aluminium weighs roughly a third of copper for the same volume, and on large feeders that difference changes drum sizes, pulling equipment and support loads. On long runs the material cost is also lower.
The engineering compromise is conductivity. Aluminium carries about 61 % of the current of copper for the same cross-section, so a larger conductor is needed for an equivalent rating — typically one or two standard sizes up. The cable is still lighter and lower in material cost at that size.
Termination needs attention. Aluminium forms an oxide layer quickly, so joints must use bimetallic lugs or approved transition compounds, and the conductor should be brushed and terminated promptly. In damp or coastal environments, compound-filled glands are preferred.
The construction is otherwise the same as a copper cable: XLPE insulation for a 90 °C conductor rating, cores laid up with fillers, and a PVC, PE or LSZH sheath. Three-core and 3+1 configurations are common for distribution feeders.
Specification table
| Standard | IEC 60502-1, IEC 60228 |
|---|---|
| Rated voltage | 0.6/1 kV (U0/U) |
| Conductor | Class 1 solid or Class 2 stranded aluminium |
| Cross-section | 16 – 400 mm² |
| Insulation | XLPE (90 °C) or PVC (70 °C) |
| Cores | 1, 3, 3+1, 4, 4+1 |
| Sheath | PVC ST2, PE or LSZH |
| Temperature range | −15 °C to +90 °C (XLPE) |
| Bending radius | 12 × overall diameter |
| Termination | Bimetallic lugs or approved transition compound |
| Packing | Drum, 500 m / 1000 m or project lengths |
Available constructions
| Construction | Typical use |
|---|---|
| Al / XLPE / PVC | General distribution feeders indoors and in ducts. |
| Al / XLPE / PE | Wet or buried routes where moisture resistance is required. |
| Al / XLPE / STA / PE | Armoured aluminium feeder for direct burial. |
| Al / PVC / PVC | Economical 70 °C construction for lightly loaded circuits. |
Where it is used
- Long feeders — Site distribution where copper weight would need special handling.
- Industrial parks — Sub-main supplies between buildings and distribution rooms.
- Pumping stations — Feeds to pumps and controls in remote or buried routes.
- Rural distribution — Low voltage distribution where cost per metre is decisive.
How it ships
- Drums marked with length, size and gross weight.
- End caps sealed to prevent moisture ingress during shipping.
- Bimetallic lugs and transition kits can be quoted with the cable.
- Drum schedule issued before shipment.
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsQuestions buyers ask about this cable
How much larger must the aluminium conductor be?
Can aluminium and copper be joined directly?
Is aluminium cable suitable for frequent movement?
Does aluminium cable need special support?
Request datasheet & price
Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.
Get a Quote WhatsApp UsOften specified with this cable
Related constructions from the same or a neighbouring family.
All products
0.6/1kV PVC/XLPE Insulated LV Power Cable
The general-purpose 0.6/1kV cable for final circuits: copper conductor, PVC or XLPE insulation, 1 to 5 cores, PVC, PE or LSZH sheath.
View product →
Steel Tape Armoured LV Cable
STA and DSTA 0.6/1kV cable for direct burial and exposed routes: XLPE insulation, PVC bedding, galvanised steel tape, PE or PVC outer sheath.
View product →Request a quotation for Aluminum Conductor LV Cable
Share the application, voltage, core count, conductor size, screen or armour, sheath and delivery destination. Our engineering team replies within one business day.