Skip to content
IEC 60502-1 · IEC 60228  ·  LV Power, Armoured, LSZH & Fire-Resistant Cable Manufacturer
ZMS Cable logo
Home  /  Products  /  Armoured LV Cables  /  Steel Tape Armoured LV Cable
Armoured LV Cables

Steel Tape Armoured Cable, 0.6/1kV

0.6/1kV XLPE cable with a galvanised steel tape armour over a PVC bedding, finished with a PE or PVC sheath for buried and exposed routes.

Voltage0.6/1 kV
ArmourSTA / DSTA
Size4 – 400 mm²
SheathPE / PVC
StandardIEC 60502-1
Description

Construction and behaviour

Steel tape armour is the standard answer to a route that cannot be protected by ducting. Two galvanised tapes are applied helically over the cable bedding, overlapping so that the layer is continuous, and then covered by an extruded sheath. The result resists impact, compression and rodent attack, and provides a metallic earth path along the route.

The bedding matters as much as the armour. It cushions the tapes against the insulation during bending and prevents the tape edges from damaging the cores. A cable that skips the bedding may pass a factory test and still fail after a few years in wet ground.

Double tape (DSTA) is used where the specification calls for higher impact resistance or where the tape thickness would otherwise be insufficient for the required short-circuit rating. Single tape is adequate for ordinary burial depths and normal traffic loads.

Sheath choice follows the soil: PE for permanently wet, sandy or chemically active ground, PVC ST2 where flame retardance or UV exposure governs. Black is standard; the sheath carries embossed or inkjet identification along its length.

Technical parameters

Specification table

StandardIEC 60502-1, IEC 60228
Rated voltage0.6/1 kV (U0/U)
ConductorClass 2 stranded copper; aluminium on request
Cross-section4 – 400 mm²
InsulationXLPE (90 °C) or PVC (70 °C)
BeddingExtruded PVC or PE inner covering
ArmourGalvanised steel tape, single or double layer
Outer sheathPE or PVC ST2, black, 1.8 – 3.0 mm nominal
Bending radius12 × overall diameter (tape armour)
ApplicationDirect burial, cable trench, outdoor yard, duct
PackingDrum, 500 m / 1000 m or project lengths
Standards: manufactured and tested to IEC 60502-1 and IEC 60228. Type test reports and routine test results are issued with the batch documents.
Options

Available constructions

ConstructionTypical use
Cu / XLPE / STA / PEDirect burial in wet or chemically active soil.
Cu / XLPE / DSTA / PEHigher impact resistance, deeper burial, vehicle loading.
Cu / XLPE / STA / PVCBuried or exposed routes where flame retardance is also required.
Al / XLPE / STA / PELong feeders where weight and cost matter.
Applications

Where it is used

  • Buried feeders — Workshop, pump house and site building supplies without ducting.
  • Outdoor yards — Routes crossing vehicle areas, storage yards and exposed ground.
  • Cable trenches — Shared trenches where later works may damage an unarmoured cable.
  • Ring mains — Site distribution rings with multiple buried sections.
Packing & delivery

How it ships

  • Drums marked with cable description, length, drum number and gross weight.
  • End caps sealed against moisture ingress during sea freight.
  • Drum schedule and packing list issued with the shipping documents.
  • Armoured glands and earth tags can be supplied with the order.

Request datasheet & price

Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.

Get a Quote WhatsApp Us
Response< 24 h
MOQOn request
Technical FAQ

Questions buyers ask about this cable

How deep should armoured cable be buried?
Burial depth is set by local regulation and by the risk of later excavation — commonly 0.6 to 0.8 m with sand bedding and warning tape. The armour protects against impact, not against a mechanical digger, so marking and route records still matter.
Can the armour be used as the earth conductor?
It can carry fault current, but the cross-section must satisfy the disconnection requirements of the installation. Many specifications require a separate earth core, which is why 3+1 and 4+1 constructions are common for buried feeders.
Does the cable come with glands?
Glands and lugs are not part of the cable but we can supply them matched to the cable diameter and armour type, with an earth tag for the armour bond.
Is STA cable suitable for a vertical riser?
Tape armour provides radial protection but limited tensile strength. For long vertical runs specify steel wire armour (SWA), which carries the cable weight.

Request datasheet & price

Send the project specification and we will confirm construction, standard and delivery schedule. Samples for approval can be arranged.

Get a Quote WhatsApp Us
Response< 24 h
MOQOn request
Related products

Often specified with this cable

Related constructions from the same or a neighbouring family.

All products
Aluminium conductor low voltage power cable with XLPE insulation
LV Power Cables (0.6/1kV)

Aluminum Conductor LV Cable

0.6/1kV aluminium conductor cable for long feeders where weight and cost matter: XLPE insulation, 16 to 400 mm², PVC or PE sheath.

0.6/1 kVAluminium16 – 400 mm²
View product →

Request a quotation for Steel Tape Armoured LV Cable

Share the application, voltage, core count, conductor size, screen or armour, sheath and delivery destination. Our engineering team replies within one business day.

This field is required.
This field is required.
This field is required.